RAYCHEM HWAT-T55 thermostat is designed for use with HWAT-L, -M or -R. Maximum circuit length is limited to 50m.
• Supply voltage – 230 VAC, +10%/-10%, 50 Hz
• Relay output heating cable – 230 VAC, max 16A
• Power consumption – max. 5VA
• Terminal size – 2,5 mm², screwed
• Temperature setting range (consider local hygienic standard) – 40-60°C; default value is 55°C
• Storage temperature – -20°C to +55°C
• Switching hysteresis – +/–2K
• Ambient temperature-range operation – 0°C to +40°C
• Accuracy – +/- 1,5 K including temperature probe -20°C to +55°C
Product code: 1244-015722